Industrial Automation
Your Current Location: Home > Products > Industrial Automation
  • M60-1S

    Profile

    M60 protection controller is designed to provide full-scale protections and controls of low-voltage asynchronous motor and increasing safety motor rated below 800A, 50Hz, 380VAC. M60 measures the electrical parameters of motors, operates and controls the motors ,and equipped with the history record management and remote communication function.

     

    M60 products portfolio: standard M60-1S and M60-3S, popular M60-2M and integrated M60-2P. With different infrastructure, installation, and functions, these four types of protector controllers can meet different requirements of customers in low-voltage protection area.

     

    Features

    Variety of product portfolio to suit customers' needs

    Recording function to record the instant data before and after the faults for fault analysis purpose

    Flexible protection functions configuration to ensure the safe and continuous production

    Automatic software and hardware inspection to increase the stability and reliability

    Remote or local operation on parameters setup, motor start, stop, and reset

    Detection on the motor start status automatically to avoid malfunction

    Configured with large size LCD panel for on-site operation (optional)

     

    Technical Specification of M60-1S

    Input (M60-1S)

    Input Current: 5A

    Remote digital signal input: 1 channel (dry contact)

     

    Output (M60-1S)

    RS-485 output: 1 channel

    Analog output: M60-1S, 1 channel (4-20mA or 0-5V)

                Relay output: 2 channels (dry contact)

    Contact capacity of control output relay: 10A/250VAC

    Contact capacity of alarm output relay: 10A/250VAC

     

    Measurement Record (M60-1S)

    Accuracy: I, class 0.5

    Accumulated operating time on record (Max.): 9999days

     

    Size & Weight: (M60-1S)

    Installation: Panel mounting

    Dimensional size: 96mmX48mmX76mm

    Installation size: 94mmX46mm

    Weight: 450g

     

    Environment

    Auxiliary power supply: 85~265VAC/DC

    Total power consumption: 3VAM60-1S/3S

                         

    Operation temperature: -20 ~ +60

    Storage temperature: -40 ~ +85

    Operation humidity: 90%RH

    Storage humidity: 95%RH

    Protection Function:

    Function

    Status

    Item

    Content

    M60-1S

    M60-2S

    M60-2M

    M60-2P

    Overtime start protection

    Programmable

    Allowed startup time

    0-80s

    Yes

    Yes

    Yes

    Yes

    Protection method

    2

    Short circuit protection

    Programmable

    Fault setting range

    4-12le

    Yes

    Yes

    Yes

    Yes

    Execution delay time

    0.1-0.5s

    Protection method

    0, 2

    Locked rotor protection

    Programmable

    Fault setting range

    200-950%le

    Yes

    Yes

    Yes

    Yes

    Warning setting range

    150-255%le

    Execution delay time

    0.1-25.5s

    Protection method

    0, 1, 2, 4

    Underload protection

    Programmable

    Setting range

    20-95%le

    Yes

    Yes

    Yes

    Yes

    Execution delay time

    0.1-60s

    Protection method

    0, 1, 2, 3

    Overload protection

    Programmable

    Setting range

    105-150%le

    Yes

    Yes

    Yes

    Yes

    Execution delay time

    0.1-250s

    Protection method

    0, 1, 2, 3, 4

    Thermal by overload

    Must

    Setting range

    1-105%θb

    Yes

    Yes

    Yes

    Yes

    Protection method

    4

    tE time protection (Increased Safty Motor)

    Programmable

    tE time

    1.0-15s

    Yes

    Yes

    Yes

    Yes

    Protection method

    4

    Unbalance protection (phase failure)

    Programmable

    Setting range

    10%-60%

    Yes

    Yes

    Yes

    Yes

    Execution delay time

    0.1-30s

    Protection method

    0, 2, 4

    Over power protection

    Programmable

    Setting range

    101-120%Pe

     

     

    Yes

    Yes

    Execution delay time

    0.1-200s

    Protection method

    0, 1, 2, 3

    Under power protection

    Programmable

    Setting range

    30-80%Pe

     

     

    Yes

    Yes

    Execution delay time

    0.1-200s

    Protection method

    0, 1, 2, 3

    Over power factor protection

    Programmable

    Setting range

    0.01-1.00

     

     

    Yes

    Yes

    Execution delay time

    0.1-25.5s

    Protection method

    0, 1, 2, 3

    Under power factor protection

    Programmable

    Setting range

    0.01-1.00

     

     

    Yes

    Yes

    Execution delay time

    0.1-25.5s

    Protection method

    0, 1, 2, 3

    Phase reversal protection

    Porgrammable

    Execution delay time

    0.1-25.5s

     

     

    Yes

    Yes

    Protection method

    0, 2

    Under voltage protection

    Programmable

    Setting range

    45-95%Ue

     

     

    Yes

    Yes

    Execution delay time

    0.1-200s

    Protection method

    0, 1, 2, 3

    Over voltage protection

    Programmable

    Setting range

    101-120%Ue

     

     

    Yes

    Yes

    Execution delay time

    0.1-200s

    Protection method

    0, 1, 2, 3

    Leakage Current protection

    Programmable

    Setting range

    10-500mA

     

     

    Yes

    Yes

    Execution delay time

    0.1-5s

    Protection method

    0, 1, 2

    Overheat protection

    Programmable

    Execution delay time

    0.5s

     

     

     

    Yes

    Protection method

    0, 2

    Interlock protection

    Programmable

    Execution delay time

    0.1-60s

    Yes

    Yes

    Yes

    Yes

    Protection method

    2

    Connection to ground protction

    Programmable

    Setting range

    10-100%Ie

    Yes

    Yes

    Yes

    Yes

    Execution delay time

    0.1-5s

    Protection method

    0, 2

     

    M60-1S

    M60-3S

    M60-2M

    M60-2P

    Control function

    Direct start

     

     



    Reversing start      

     

     

     

    Y-Start

     

     

     


    Lower Voltage start

     

     

     


    Restart motors caused by Voltage fluctuation      

     

     


  • M60-3S

    Profile

    M60 protection controller is designed to provide full-scale protections and controls of low-voltage asynchronous motor and increasing safety motor rated below 800A, 50Hz, 380VAC. M60 measures the electrical parameters of motors, operates and controls the motors ,and equipped with the history record management and remote communication function.

     

    M60 products portfolio: standard M60-1S and M60-3S, popular M60-2M and integrated M60-2P. With different infrastructure, installation, and functions, these four types of protector controllers can meet different requirements of customers in low-voltage protection area.

     

    Features

    Variety of product portfolio to suit customers' needs

    Recording function to record the instant data before and after the faults for fault analysis purpose

    Flexible protection functions configuration to ensure the safe and continuous production

    Automatic software and hardware inspection to increase the stability and reliability

    Remote or local operation on parameters setup, motor start, stop, and reset

    Detection on the motor start status automatically to avoid malfunction

    Configured with large size LCD panel for on-site operation (optional)

     

    Technical Specification of M60-3S

    Input (M60-3S)

    Input Current: 1A, 5A,6.3A, 25A, 50A, 100A,160A, 200A, 250A

    Remote digital signal input: 1 channel (dry contact)

     

    Output (M60-3S)

    RS-485 output: 1 channel

    Analog output: M60-3S, 2 channels (4-20mA or 0-5V)

    Relay output: 2 channels (dry contact)

    Contact capacity of control output relay: 10A/250VAC

    Contact capacity of alarm output relay: 10A/250VAC

     

    Measurement Record (M60-3S)

    Accuracy: I, class 0.5

    Accumulated operating time on record (Max.): 9999days

     

    Size & Weight: (M60-3S)

    Installation: Panel mounting

    Dimensional size: 96mmX48mmX76mm

    Installation size: 94mmX46mm

    Weight: 450g

     

    Environment:

    Auxiliary power supply: 85~265VAC/DC

    Total power consumption: 3VAM60-3S

    Operation temperature: -20 ~ +60

    Storage temperature: -40 ~ +85

    Operation humidity: 90%RH

    Storage humidity: 95%RH

     

    Protection Function:

     

    Function

    Status

    Item

    Content

    M60-1S

    M60-2S

    M60-2M

    M60-2P

    Overtime start protection

    Programmable

    Allowed startup time

    0-80s

    Yes

    Yes

    Yes

    Yes

    Protection method

    2

    Short circuit protection

    Programmable

    Fault setting range

    4-12le

    Yes

    Yes

    Yes

    Yes

    Execution delay time

    0.1-0.5s

    Protection method

    0, 2

    Locked rotor protection

    Programmable

    Fault setting range

    200-950%le

    Yes

    Yes

    Yes

    Yes

    Warning setting range

    150-255%le

    Execution delay time

    0.1-25.5s

    Protection method

    0, 1, 2, 4

    Underload protection

    Programmable

    Setting range

    20-95%le

    Yes

    Yes

    Yes

    Yes

    Execution delay time

    0.1-60s

    Protection method

    0, 1, 2, 3

    Overload protection

    Programmable

    Setting range

    105-150%le

    Yes

    Yes

    Yes

    Yes

    Execution delay time

    0.1-250s

    Protection method

    0, 1, 2, 3, 4

    Thermal by overload

    Must

    Setting range

    1-105%θb

    Yes

    Yes

    Yes

    Yes

    Protection method

    4

    tE time protection (Increased Safty Motor)

    Programmable

    tE time

    1.0-15s

    Yes

    Yes

    Yes

    Yes

    Protection method

    4

    Unbalance protection (phase failure)

    Programmable

    Setting range

    10%-60%

    Yes

    Yes

    Yes

    Yes

    Execution delay time

    0.1-30s

    Protection method

    0, 2, 4

    Over power protection

    Programmable

    Setting range

    101-120%Pe

     

     

    Yes

    Yes

    Execution delay time

    0.1-200s

    Protection method

    0, 1, 2, 3

    Under power protection

    Programmable

    Setting range

    30-80%Pe

     

     

    Yes

    Yes

    Execution delay time

    0.1-200s

    Protection method

    0, 1, 2, 3

    Over power factor protection

    Programmable

    Setting range

    0.01-1.00

     

     

    Yes

    Yes

    Execution delay time

    0.1-25.5s

    Protection method

    0, 1, 2, 3

    Under power factor protection

    Programmable

    Setting range

    0.01-1.00

     

     

    Yes

    Yes

    Execution delay time

    0.1-25.5s

    Protection method

    0, 1, 2, 3

    Phase reversal protection

    Porgrammable

    Execution delay time

    0.1-25.5s

     

     

    Yes

    Yes

    Protection method

    0, 2

    Under voltage protection

    Programmable

    Setting range

    45-95%Ue

     

     

    Yes

    Yes

    Execution delay time

    0.1-200s

    Protection method

    0, 1, 2, 3

    Over voltage protection

    Programmable

    Setting range

    101-120%Ue

     

     

    Yes

    Yes

    Execution delay time

    0.1-200s

    Protection method

    0, 1, 2, 3

    Leakage Current protection

    Programmable

    Setting range

    10-500mA

     

     

    Yes

    Yes

    Execution delay time

    0.1-5s

    Protection method

    0, 1, 2

    Overheat protection

    Programmable

    Execution delay time

    0.5s

     

     

     

    Yes

    Protection method

    0, 2

    Interlock protection

    Programmable

    Execution delay time

    0.1-60s

    Yes

    Yes

    Yes

    Yes

    Protection method

    2

    Connection to ground protction

    Programmable

    Setting range

    10-100%Ie

    Yes

    Yes

    Yes

    Yes

    Execution delay time

    0.1-5s

    Protection method

    0, 2

     

     

    M60-1S

    M60-3S

    M60-2M

    M60-2P

    Control function

    Direct start

     

     

    Unbalanced Current ratio

  • M60-2M

    Profile

    M60 protection controller is designed to provide full-scale protections and controls of low-voltage asynchronous motor and increasing safety motor rated below 800A, 50Hz, 380VAC. M60 measures the electrical parameters of motors, operates and controls the motors ,and equipped with the history record management and remote communication function.

     

    M60 products portfolio: standard M60-1S and M60-3S, popular M60-2M and integrated M60-2P. With different infrastructure, installation, and functions, these four types of protector controllers can meet different requirements of customers in low-voltage protection area.

     

    Features

    Variety of product portfolio to suit customers' needs

    Recording function to record the instant data before and after the faults for fault analysis purpose

    Flexible protection functions configuration to ensure the safe and continuous production

    Automatic software and hardware inspection to increase the stability and reliability

    Remote or local operation on parameters setup, motor start, stop, and reset

    Detection on the motor start status automatically to avoid malfunction

    Configured with large size LCD panel for on-site operation (optional)

     

    Technical Specification of M60-2M

    Input (M60-2M)

    Input Current: 1A, 5A,6.3A, 25A, 50A, 100A,160A, 200A, 250A

    Input Voltage: 380VAC/50Hz

    Remote digital signal input: 7 channels (220VAC)

     

    Output (M60-2M)

    RS-485 output: 1 channel

    Analog output: 1 channel (4-20mA or 0-5V)

    Relay output: 4 channels (dry contact)

    Contact capacity of control output relay: 10A/250VAC

     

    Measurement Record (M60-2M)

    Accuracy: U, I, F class 0.5

    Accuracy: cosΦ, P, Q class 1

    Accuracy: Ep class 2

    Accumulated operating time on record (Max.): 65535 hours.

     

    Size & Weight: (M60-2M)

    Installation: 35mm Din rail, with 3 M4 bolts to support

    Dimensional size: 75mmX80mmX103mm (100A )

    Dimensional Size: 75mmX102mmX140mm (100A-250A)

    Operating panel size: 76mmX61mmX17mm

    Weight: 450g ( 100A )

    Weight: 560g ( 250A )

     

    Restart function after Voltage Fluctuation (M60-2M)

    Voltage fluctuation allowing time: 0.1-25.5S

    Restart delay time: 0.1-25.5S

    Time adjustment step: 0.1S

    Lower Voltage setup scope:80%-89%Ue

     

    Environment

    Auxiliary power supply: 85~265VAC/DC

    Total power consumption:5VAM60-2M

    Operation temperature: -20 ~ +60

    Storage temperature: -40 ~ +85

    Operation humidity: 90%RH

    Storage humidity: 95%RH

     

    Protection Function:

     

    Function

    Status

    Item

    Content

    M60-1S

    M60-2S

    M60-2M

    M60-2P

    Overtime start protection

    Programmable

    Allowed startup time

    0-80s

    Yes

    Yes

    Yes

    Yes

    Protection method

    2

    Short circuit protection

    Programmable

    Fault setting range

    4-12le

    Yes

    Yes

    Yes

    Yes

    Execution delay time

    0.1-0.5s

    Protection method

    0, 2

    Locked rotor protection

    Programmable

    Fault setting range

    200-950%le

    Yes

    Yes

    Yes

    Yes

    Warning setting range

    150-255%le

    Execution delay time

    0.1-25.5s

    Protection method

    0, 1, 2, 4

    Underload protection

    Programmable

    Setting range

    20-95%le

    Yes

    Yes

    Yes

    Yes

    Execution delay time

    0.1-60s

    Protection method

    0, 1, 2, 3

    Overload protection

    Programmable

    Setting range

    105-150%le

    Yes

    Yes

    Yes

    Yes

    Execution delay time

    0.1-250s

    Protection method

    0, 1, 2, 3, 4

    Thermal by overload

    Must

    Setting range

    1-105%θb

    Yes

    Yes

    Yes

    Yes

    Protection method

    4

    tE time protection (Increased Safty Motor)

    Programmable

    tE time

    1.0-15s

    Yes

    Yes

    Yes

    Yes

    Protection method

    4

    Unbalance protection (phase failure)

    Programmable

    Setting range

    10%-60%

    Yes

    Yes

    Yes

    Yes

    Execution delay time

    0.1-30s

    Protection method

    0, 2, 4

    Over power protection

    Programmable

    Setting range

    101-120%Pe

     

     

    Yes

    Yes

    Execution delay time

    0.1-200s

    Protection method

    0, 1, 2, 3

    Under power protection

    Programmable

    Setting range

    30-80%Pe

     

     

    Yes

    Yes

    Execution delay time

    0.1-200s

    Protection method

    0, 1, 2, 3

    Over power factor protection

    Programmable

    Setting range

    0.01-1.00

     

     

    Yes

    Yes

    Execution delay time

    0.1-25.5s

    Protection method

    0, 1, 2, 3

    Under power factor protection

    Programmable

    Setting range

    0.01-1.00

     

     

    Yes

    Yes

    Execution delay time

    0.1-25.5s

    Protection method

    0, 1, 2, 3

    Phase reversal protection

    Porgrammable

    Execution delay time

    0.1-25.5s

     

     

    Yes

    Yes

    Protection method

    0, 2

    Under voltage protection

    Programmable

    Setting range

    45-95%Ue

     

     

    Yes

    Yes

    Execution delay time

    0.1-200s

    Protection method

    0, 1, 2, 3

    Over voltage protection

    Programmable

    Setting range

    101-120%Ue

     

     

    Yes

    Yes

    Execution delay time

    0.1-200s

    Protection method

    0, 1, 2, 3

    Leakage Current protection

    Programmable

    Setting range

    10-500mA

     

     

    Yes

    Yes

    Execution delay time

    0.1-5s

    Protection method

    0, 1, 2

    Overheat protection

    Programmable

    Execution delay time

    0.5s

     

     

     

    Yes

    Protection method

    0, 2

    Interlock protection

    Programmable

    Execution delay time

    0.1-60s

    Yes

    Yes

    Yes

    Yes

    Protection method

    2

    Connection to ground protction

    Programmable

    Setting range

    10-100%Ie

    Yes

    Yes

    Yes

    Yes

    Execution delay time

    0.1-5s

    Protection method

    0, 2

     

     

    M60-1S

    M60-3S

    M60-2M

    M60-2P

    Control function

    Direct start

     

     

    Reversing start      

     

     

     

    Y-Start

     

     

     

    Lower Voltage start

     

     

     

    Restart motors caused by Voltage fluctuation      

     

     

    Emergency fault output

     

     

    Local/remote command of start, stop

     

     

    Measurement function

    Operating Current

    Unbalanced Current ratio

    Voltage, frequency, power, power factorleakage current   

     

     

    No. of contact executions

     

     

    Status of contacts

     

     

    Record Function

    Latest 10 start/stop record

     

     

    Clock

    Clock

    Latest 10 alarm record  

    No clock

    No clock

    Clock

    Clock

    Latest 10 trip record

    No clock

    No clock

    Clock

    Clock

    Latest 10 restart record caused by Voltage fluctuation

     

     

    Clock

    Clock

    Max. and min. parameters records in the protection execution

    Accumulated operating time of motor  

    Communication Function

    RS-485 com. Port

    Modbus protocol   

    Profibus protocol  

     

     

     

    Remark:

    M60-3S performs the same function as M60-1S, except that M60-3S has built-in CT, M60-1S has exterior CT with 5A input.

     

     

  • M60-2P

    Profile

    M60 protection controller is designed to provide full-scale protections and controls of low-voltage asynchronous motor and increasing safety motor rated below 800A, 50Hz, 380VAC. M60 measures the electrical parameters of motors, operates and controls the motors ,and equipped with the history record management and remote communication function.

     

    M60 products portfolio: standard M60-1S and M60-3S, popular M60-2M and integrated M60-2P. With different infrastructure, installation, and functions, these four types of protector controllers can meet different requirements of customers in low-voltage protection area.

     

    Features

    Variety of product portfolio to suit customers' needs

    Recording function to record the instant data before and after the faults for fault analysis purpose

    Flexible protection functions configuration to ensure the safe and continuous production

    Automatic software and hardware inspection to increase the stability and reliability

    Remote or local operation on parameters setup, motor start, stop, and reset

    Detection on the motor start status automatically to avoid malfunction

    Configured with large size LCD panel for on-site operation (optional)

     

    Technical Specification of M60-2P

    Input (M60-2P)

    Input Current: 1A, 6.3A,25A, 100A, 250A,500A, 800A

    Input Voltage: 380VAC/50Hz

    Remote digital signal input: 11 channels (dry contact)

     

    Output (M60-2P)

    RS-485 output: 2 channels

    Analog output: 2 channels (4-20mA or 0-5V)

    Relay output: 6 channels (dry contact)

    Contact capacity of control output relay: 10A/250VAC

    Contact capacity of alarm output relay: 5A/250VAC

     

    Measurement Record (M60-2P)

    Accuracy: U, I, F class 0.5

    Accuracy: cosΦ, P, Q class 1

    Accuracy: Ep class 2

    Accumulated operating time on record (Max.): 65535 hours

     

    Size & Weight: (M60-2P)

    Installation (M60-2P): 35mm Din rail, with 4 M4 bolts to support

    Installation (CT): with 4 M4 bolts to support

    Dimensional size (M60-2P): 82mmX100mmX106mm

    Operating panel size: 76mmX61mmX28mm

    Weight: 450gnot including CT

    Remark: The size and weight of CT is decided by input current.

     

    Restart function after Voltage Fluctuation (M60-2P)

    Voltage fluctuation allowing time: 0.1-25.5S

    Restart delay time: 0.1-25.5S

    Time adjustment step: 0.1S

    Lower Voltage setup scope:80%-89%Ue

     

    Environment:

    Auxiliary power supply: 85~265VAC/DC

    Total power consumption: 8VAM60-2P

    Operation temperature: -20 ~ +60

    Storage temperature: -40 ~ +85

    Operation humidity: 90%RH

    Storage humidity: 95%RH

     

    Protection Function:

     

    Function

    Status

    Item

    Content

    M60-1S

    M60-2S

    M60-2M

    M60-2P

    Overtime start protection

    Programmable

    Allowed startup time

    0-80s

    Yes

    Yes

    Yes

    Yes

    Protection method

    2

    Short circuit protection

    Programmable

    Fault setting range

    4-12le

    Yes

    Yes

    Yes

    Yes

    Execution delay time

    0.1-0.5s

    Protection method

    0, 2

    Locked rotor protection

    Programmable

    Fault setting range

    200-950%le

    Yes

    Yes

    Yes

    Yes

    Warning setting range

    150-255%le

    Execution delay time

    0.1-25.5s

    Protection method

    0, 1, 2, 4

    Underload protection

    Programmable

    Setting range

    20-95%le

    Yes

    Yes

    Yes

    Yes

    Execution delay time

    0.1-60s

    Protection method

    0, 1, 2, 3

    Overload protection

    Programmable

    Setting range

    105-150%le

    Yes

    Yes

    Yes

    Yes

    Execution delay time

    0.1-250s

    Protection method

    0, 1, 2, 3, 4

    Thermal by overload

    Must

    Setting range

    1-105%θb

    Yes

    Yes

    Yes

    Yes

    Protection method

    4

    tE time protection (Increased Safty Motor)

    Programmable

    tE time

    1.0-15s

    Yes

    Yes

    Yes

    Yes

    Protection method

    4

    Unbalance protection (phase failure)

    Programmable

    Setting range

    10%-60%

    Yes

    Yes

    Yes

    Yes

    Execution delay time

    0.1-30s

    Protection method

    0, 2, 4

    Over power protection

    Programmable

    Setting range

    101-120%Pe

     

     

    Yes

    Yes

    Execution delay time

    0.1-200s

    Protection method

    0, 1, 2, 3

    Under power protection

    Programmable

    Setting range

    30-80%Pe

     

     

    Yes

    Yes

    Execution delay time

    0.1-200s

    Protection method

    0, 1, 2, 3

    Over power factor protection

    Programmable

    Setting range

    0.01-1.00

     

     

    Yes

    Yes

    Execution delay time

    0.1-25.5s

    Protection method

    0, 1, 2, 3

    Under power factor protection

    Programmable

    Setting range

    0.01-1.00

     

     

    Yes

    Yes

    Execution delay time

    0.1-25.5s

    Protection method

    0, 1, 2, 3

    Phase reversal protection

    Porgrammable

    Execution delay time

    0.1-25.5s

     

     

    Yes

    Yes

    Protection method

    0, 2

    Under voltage protection

    Programmable

    Setting range

    45-95%Ue

     

     

    Yes

    Yes

    Execution delay time

    0.1-200s

    Protection method

    0, 1, 2, 3

    Over voltage protection

    Programmable

    Setting range

    101-120%Ue

     

     

    Yes

    Yes

    Execution delay time

    0.1-200s

    Protection method

    0, 1, 2, 3

    Leakage Current protection

    Programmable

    Setting range

    10-500mA

     

     

    Yes

    Yes

    Execution delay time

    0.1-5s

    Protection method

    0, 1, 2

    Overheat protection

    Programmable

    Execution delay time

    0.5s

     

     

     

    Yes

    Protection method

    0, 2

    Interlock protection

    Programmable

    Execution delay time

    0.1-60s

    Yes

    Yes

    Yes

    Yes

    Protection method

    2

    Connection to ground protction

    Programmable

    Setting range

    10-100%Ie

    Yes

    Yes

    Yes

    Yes

    Execution delay time

    0.1-5s

    Protection method

    0, 2

     

    M60-1S

    M60-3S

    M60-2M

    M60-2P

    Control function

    Direct start

     

     

    Reversing start      

     

     

     


    Y-Start

     

     

     


    Lower Voltage start

     

     

     

    Restart motors caused by Voltage fluctuation      

     

     


    Emergency fault output

     

     

    Local/remote command of start, stop

     

     

    Measurement function

    Operating Current

    Unbalanced Current ratio

    Voltage, frequency, power, power factorleakage current      

     

     

    No. of contact executions

     

     

    Status of contacts

     

     

    Record Function

    Latest 10 start/stop record

     

     

    Clock

    Clock

    Latest 10 alarm record  

    No clock

    No clock

    Clock

    Clock

    Latest 10 trip record

    No clock

    No clock

    Clock

    Clock

    Latest 10 restart record caused by Voltage fluctuation

     

     

    Clock

    Clock

    Max. and min. parameters records in the protection execution

    Accumulated operating time of motor  

    Communication Function

    RS-485 com. Port

    Modbus protocol   

    Profibus protocol  

     

     

     

    Remark:

    M60-3S performs the same function as M60-1S, except that M60-3S has built-in CT, M60-1S has exterior CT with 5A input.

     

     