M60 protection controller is designed to provide full-scale protections and controls of low-voltage asynchronous motor and increasing safety motor rated below 800A, 50Hz, 380VAC. M60 measures the electrical parameters of motors, operates and controls the motors ,and equipped with the history record management and remote communication function.

 

M60 products portfolio: standard M60-1S and M60-3S, popular M60-2M and integrated M60-2P. With different infrastructure, installation, and functions, these four types of protector controllers can meet different requirements of customers in low-voltage protection area.

 

Features

Variety of product portfolio to suit customers' needs

Recording function to record the instant data before and after the faults for fault analysis purpose

Flexible protection functions configuration to ensure the safe and continuous production

Automatic software and hardware inspection to increase the stability and reliability

Remote or local operation on parameters setup, motor start, stop, and reset

Detection on the motor start status automatically to avoid malfunction

Configured with large size LCD panel for on-site operation (optional)

 

Technical Specification of M60-2P

Input (M60-2P)

Input Current: 1A, 6.3A,25A, 100A, 250A,500A, 800A

Input Voltage: 380VAC/50Hz

Remote digital signal input: 11 channels (dry contact)

 

Output (M60-2P)

RS-485 output: 2 channels

Analog output: 2 channels (4-20mA or 0-5V)

Relay output: 6 channels (dry contact)

Contact capacity of control output relay: 10A/250VAC

Contact capacity of alarm output relay: 5A/250VAC

 

Measurement Record (M60-2P)

Accuracy: U, I, F class 0.5

Accuracy: cosΦ, P, Q class 1

Accuracy: Ep class 2

Accumulated operating time on record (Max.): 65535 hours

 

Size & Weight: (M60-2P)

Installation (M60-2P): 35mm Din rail, with 4 M4 bolts to support

Installation (CT): with 4 M4 bolts to support

Dimensional size (M60-2P): 82mmX100mmX106mm

Operating panel size: 76mmX61mmX28mm

Weight: 450gnot including CT

Remark: The size and weight of CT is decided by input current.

 

Restart function after Voltage Fluctuation (M60-2P)

Voltage fluctuation allowing time: 0.1-25.5S

Restart delay time: 0.1-25.5S

Time adjustment step: 0.1S

Lower Voltage setup scope:80%-89%Ue

 

Environment:

Auxiliary power supply: 85~265VAC/DC

Total power consumption: 8VAM60-2P

Operation temperature: -20 ~ +60

Storage temperature: -40 ~ +85

Operation humidity: 90%RH

Storage humidity: 95%RH

 

Protection Function:

 

Function

Status

Item

Content

M60-1S

M60-2S

M60-2M

M60-2P

Overtime start protection

Programmable

Allowed startup time

0-80s

Yes

Yes

Yes

Yes

Protection method

2

Short circuit protection

Programmable

Fault setting range

4-12le

Yes

Yes

Yes

Yes

Execution delay time

0.1-0.5s

Protection method

0, 2

Locked rotor protection

Programmable

Fault setting range

200-950%le

Yes

Yes

Yes

Yes

Warning setting range

150-255%le

Execution delay time

0.1-25.5s

Protection method

0, 1, 2, 4

Underload protection

Programmable

Setting range

20-95%le

Yes

Yes

Yes

Yes

Execution delay time

0.1-60s

Protection method

0, 1, 2, 3

Overload protection

Programmable

Setting range

105-150%le

Yes

Yes

Yes

Yes

Execution delay time

0.1-250s

Protection method

0, 1, 2, 3, 4

Thermal by overload

Must

Setting range

1-105%θb

Yes

Yes

Yes

Yes

Protection method

4

tE time protection (Increased Safty Motor)

Programmable

tE time

1.0-15s

Yes

Yes

Yes

Yes

Protection method

4

Unbalance protection (phase failure)

Programmable

Setting range

10%-60%

Yes

Yes

Yes

Yes

Execution delay time

0.1-30s

Protection method

0, 2, 4

Over power protection

Programmable

Setting range

101-120%Pe

 

 

Yes

Yes

Execution delay time

0.1-200s

Protection method

0, 1, 2, 3

Under power protection

Programmable

Setting range

30-80%Pe

 

 

Yes

Yes

Execution delay time

0.1-200s

Protection method

0, 1, 2, 3

Over power factor protection

Programmable

Setting range

0.01-1.00

 

 

Yes

Yes

Execution delay time

0.1-25.5s

Protection method

0, 1, 2, 3

Under power factor protection

Programmable

Setting range

0.01-1.00

 

 

Yes

Yes

Execution delay time

0.1-25.5s

Protection method

0, 1, 2, 3

Phase reversal protection

Porgrammable

Execution delay time

0.1-25.5s

 

 

Yes

Yes

Protection method

0, 2

Under voltage protection

Programmable

Setting range

45-95%Ue

 

 

Yes

Yes

Execution delay time

0.1-200s

Protection method

0, 1, 2, 3

Over voltage protection

Programmable

Setting range

101-120%Ue

 

 

Yes

Yes

Execution delay time

0.1-200s

Protection method

0, 1, 2, 3

Leakage Current protection

Programmable

Setting range

10-500mA

 

 

Yes

Yes

Execution delay time

0.1-5s

Protection method

0, 1, 2

Overheat protection

Programmable

Execution delay time

0.5s

 

 

 

Yes

Protection method

0, 2

Interlock protection

Programmable

Execution delay time

0.1-60s

Yes

Yes

Yes

Yes

Protection method

2

Connection to ground protction

Programmable

Setting range

10-100%Ie

Yes

Yes

Yes

Yes

Execution delay time

0.1-5s

Protection method

0, 2

 

M60-1S

M60-3S

M60-2M

M60-2P

Control function

Direct start

 

 

Reversing start      

 

 

 


Y-Start

 

 

 


Lower Voltage start

 

 

 

Restart motors caused by Voltage fluctuation      

 

 


Emergency fault output

 

 

Local/remote command of start, stop

 

 

Measurement function

Operating Current

Unbalanced Current ratio

Voltage, frequency, power, power factorleakage current      

 

 

No. of contact executions

 

 

Status of contacts

 

 

Record Function

Latest 10 start/stop record

 

 

Clock

Clock

Latest 10 alarm record  

No clock

No clock

Clock

Clock

Latest 10 trip record

No clock

No clock

Clock

Clock

Latest 10 restart record caused by Voltage fluctuation

 

 

Clock

Clock

Max. and min. parameters records in the protection execution

Accumulated operating time of motor  

Communication Function

RS-485 com. Port

Modbus protocol   

Profibus protocol  

 

 

 

Remark:

M60-3S performs the same function as M60-1S, except that M60-3S has built-in CT, M60-1S has exterior CT with 5A input.

 

 