M60-3S
Your Current Location: Home > Products > Industrial Automation
+ Zoom

Product Name: M60-3S

Product Category: Industrial Automation

Download: M60-3S

Product Details

Profile

M60 protection controller is designed to provide full-scale protections and controls of low-voltage asynchronous motor and increasing safety motor rated below 800A, 50Hz, 380VAC. M60 measures the electrical parameters of motors, operates and controls the motors ,and equipped with the history record management and remote communication function.

 

M60 products portfolio: standard M60-1S and M60-3S, popular M60-2M and integrated M60-2P. With different infrastructure, installation, and functions, these four types of protector controllers can meet different requirements of customers in low-voltage protection area.

 

Features

Variety of product portfolio to suit customers' needs

Recording function to record the instant data before and after the faults for fault analysis purpose

Flexible protection functions configuration to ensure the safe and continuous production

Automatic software and hardware inspection to increase the stability and reliability

Remote or local operation on parameters setup, motor start, stop, and reset

Detection on the motor start status automatically to avoid malfunction

Configured with large size LCD panel for on-site operation (optional)

 

Technical Specification of M60-3S

Input (M60-3S)

Input Current: 1A, 5A,6.3A, 25A, 50A, 100A,160A, 200A, 250A

Remote digital signal input: 1 channel (dry contact)

 

Output (M60-3S)

RS-485 output: 1 channel

Analog output: M60-3S, 2 channels (4-20mA or 0-5V)

Relay output: 2 channels (dry contact)

Contact capacity of control output relay: 10A/250VAC

Contact capacity of alarm output relay: 10A/250VAC

 

Measurement Record (M60-3S)

Accuracy: I, class 0.5

Accumulated operating time on record (Max.): 9999days

 

Size & Weight: (M60-3S)

Installation: Panel mounting

Dimensional size: 96mmX48mmX76mm

Installation size: 94mmX46mm

Weight: 450g

 

Environment:

Auxiliary power supply: 85~265VAC/DC

Total power consumption: 3VAM60-3S

Operation temperature: -20 ~ +60

Storage temperature: -40 ~ +85

Operation humidity: 90%RH

Storage humidity: 95%RH

 

Protection Function:

 

Function

Status

Item

Content

M60-1S

M60-2S

M60-2M

M60-2P

Overtime start protection

Programmable

Allowed startup time

0-80s

Yes

Yes

Yes

Yes

Protection method

2

Short circuit protection

Programmable

Fault setting range

4-12le

Yes

Yes

Yes

Yes

Execution delay time

0.1-0.5s

Protection method

0, 2

Locked rotor protection

Programmable

Fault setting range

200-950%le

Yes

Yes

Yes

Yes

Warning setting range

150-255%le

Execution delay time

0.1-25.5s

Protection method

0, 1, 2, 4

Underload protection

Programmable

Setting range

20-95%le

Yes

Yes

Yes

Yes

Execution delay time

0.1-60s

Protection method

0, 1, 2, 3

Overload protection

Programmable

Setting range

105-150%le

Yes

Yes

Yes

Yes

Execution delay time

0.1-250s

Protection method

0, 1, 2, 3, 4

Thermal by overload

Must

Setting range

1-105%θb

Yes

Yes

Yes

Yes

Protection method

4

tE time protection (Increased Safty Motor)

Programmable

tE time

1.0-15s

Yes

Yes

Yes

Yes

Protection method

4

Unbalance protection (phase failure)

Programmable

Setting range

10%-60%

Yes

Yes

Yes

Yes

Execution delay time

0.1-30s

Protection method

0, 2, 4

Over power protection

Programmable

Setting range

101-120%Pe

 

 

Yes

Yes

Execution delay time

0.1-200s

Protection method

0, 1, 2, 3

Under power protection

Programmable

Setting range

30-80%Pe

 

 

Yes

Yes

Execution delay time

0.1-200s

Protection method

0, 1, 2, 3

Over power factor protection

Programmable

Setting range

0.01-1.00

 

 

Yes

Yes

Execution delay time

0.1-25.5s

Protection method

0, 1, 2, 3

Under power factor protection

Programmable

Setting range

0.01-1.00

 

 

Yes

Yes

Execution delay time

0.1-25.5s

Protection method

0, 1, 2, 3

Phase reversal protection

Porgrammable

Execution delay time

0.1-25.5s

 

 

Yes

Yes

Protection method

0, 2

Under voltage protection

Programmable

Setting range

45-95%Ue

 

 

Yes

Yes

Execution delay time

0.1-200s

Protection method

0, 1, 2, 3

Over voltage protection

Programmable

Setting range

101-120%Ue

 

 

Yes

Yes

Execution delay time

0.1-200s

Protection method

0, 1, 2, 3

Leakage Current protection

Programmable

Setting range

10-500mA

 

 

Yes

Yes

Execution delay time

0.1-5s

Protection method

0, 1, 2

Overheat protection

Programmable

Execution delay time

0.5s

 

 

 

Yes

Protection method

0, 2

Interlock protection

Programmable

Execution delay time

0.1-60s

Yes

Yes

Yes

Yes

Protection method

2

Connection to ground protction

Programmable

Setting range

10-100%Ie

Yes

Yes

Yes

Yes

Execution delay time

0.1-5s

Protection method

0, 2

 

 

M60-1S

M60-3S

M60-2M

M60-2P

Control function

Direct start

 

 

Unbalanced Current ratio

About Us

News

Products

Services

Careers

Contact Us

Copyright © 2011-2013 Shenzhen Artel Tech. Co., Ltd. All Rights Reserved About Us | Products | Partner | Links | Contact Us