Profile
M60 protection controller is designed to
provide full-scale protections and controls of low-voltage asynchronous motor
and increasing safety motor rated below
M60 products portfolio: standard M60-1S and
M60-3S, popular M60
Features
Variety of product portfolio to suit customers' needs
Recording function to record the instant data before and after the faults for fault analysis purpose
Flexible protection functions configuration to ensure the safe and continuous production
Automatic software and hardware inspection to increase the stability and reliability
Remote or local operation on parameters setup, motor start, stop, and reset
Detection on the motor start status automatically to avoid malfunction
Configured with large size LCD panel for on-site operation (optional)
Technical Specification of M60
Input
(M60
Input Current:
Input Voltage: 380VAC/50Hz
Remote digital signal input: 7 channels (220VAC)
Output
(M60
RS-485 output: 1 channel
Analog output: 1 channel (4-20mA or 0-5V)
Relay output: 4 channels (dry contact)
Contact capacity of control output relay:
Measurement
Record (M60
Accuracy: U, I, F class 0.5
Accuracy: cosΦ, P, Q class 1
Accuracy: Ep class 2
Accumulated operating time on record (Max.): 65535 hours.
Size
& Weight: (M60
Installation:
Dimensional size: 75mmX80mmX
Dimensional Size: 75mmX102mmX
Operating panel size: 76mmX61mmX
Weight:
Weight:
Restart
function after Voltage Fluctuation (M60
Voltage fluctuation allowing time: 0.1-25.5S
Restart delay time: 0.1-25.5S
Time adjustment step: 0.1S
Lower Voltage setup scope:80%-89%Ue
Environment
Auxiliary power supply: 85~265VAC/DC
Total power consumption:<5VA(M60
Operation temperature:
Storage temperature:
Operation humidity: <90%RH
Storage humidity: <95%RH
Protection Function:
Function |
Status |
Item |
Content |
M60-1S |
M60-2S |
M60 |
M60-2P |
Overtime
start protection |
Programmable |
Allowed
startup time |
0-80s |
Yes |
Yes |
Yes |
Yes |
Protection
method |
2 |
||||||
Short
circuit protection |
Programmable |
Fault
setting range |
4-12le |
Yes |
Yes |
Yes |
Yes |
Execution
delay time |
0.1-0.5s |
||||||
Protection
method |
0, 2 |
||||||
Locked
rotor protection |
Programmable |
Fault
setting range |
200-950%le |
Yes |
Yes |
Yes |
Yes |
Warning
setting range |
150-255%le |
||||||
Execution
delay time |
0.1-25.5s |
||||||
Protection
method |
0, 1, 2,
4 |
||||||
Underload
protection |
Programmable |
Setting
range |
20-95%le |
Yes |
Yes |
Yes |
Yes |
Execution
delay time |
0.1-60s |
||||||
Protection
method |
0, 1, 2,
3 |
||||||
Overload
protection |
Programmable |
Setting
range |
105-150%le |
Yes |
Yes |
Yes |
Yes |
Execution
delay time |
0.1-250s |
||||||
Protection
method |
0, 1, 2,
3, 4 |
||||||
Thermal
by overload |
Must |
Setting
range |
1-105%θb |
Yes |
Yes |
Yes |
Yes |
Protection
method |
4 |
||||||
tE time protection
(Increased Safty Motor) |
Programmable |
tE time |
1.0-15s |
Yes |
Yes |
Yes |
Yes |
Protection
method |
4 |
||||||
Unbalance
protection (phase failure) |
Programmable |
Setting
range |
10%-60% |
Yes |
Yes |
Yes |
Yes |
Execution
delay time |
0.1-30s |
||||||
Protection
method |
0, 2, 4 |
||||||
Over
power protection |
Programmable |
Setting
range |
101-120%Pe |
|
|
Yes |
Yes |
Execution
delay time |
0.1-200s |
||||||
Protection
method |
0, 1, 2,
3 |
||||||
Under
power protection |
Programmable |
Setting
range |
30-80%Pe |
|
|
Yes |
Yes |
Execution
delay time |
0.1-200s |
||||||
Protection
method |
0, 1, 2,
3 |
||||||
Over
power factor protection |
Programmable |
Setting
range |
0.01-1.00 |
|
|
Yes |
Yes |
Execution
delay time |
0.1-25.5s |
||||||
Protection
method |
0, 1, 2,
3 |
||||||
Under
power factor protection |
Programmable |
Setting
range |
0.01-1.00 |
|
|
Yes |
Yes |
Execution
delay time |
0.1-25.5s |
||||||
Protection
method |
0, 1, 2,
3 |
||||||
Phase
reversal protection |
Porgrammable |
Execution
delay time |
0.1-25.5s |
|
|
Yes |
Yes |
Protection
method |
0, 2 |
||||||
Under
voltage protection |
Programmable |
Setting
range |
45-95%Ue |
|
|
Yes |
Yes |
Execution
delay time |
0.1-200s |
||||||
Protection
method |
0, 1, 2,
3 |
||||||
Over
voltage protection |
Programmable |
Setting
range |
101-120%Ue |
|
|
Yes |
Yes |
Execution
delay time |
0.1-200s |
||||||
Protection
method |
0, 1, 2,
3 |
||||||
Leakage
Current protection |
Programmable |
Setting
range |
10-500mA |
|
|
Yes |
Yes |
Execution
delay time |
0.1-5s |
||||||
Protection
method |
0, 1, 2 |
||||||
Overheat
protection |
Programmable |
Execution
delay time |
0.5s |
|
|
|
Yes |
Protection
method |
0, 2 |
||||||
Interlock
protection |
Programmable |
Execution
delay time |
0.1-60s |
Yes |
Yes |
Yes |
Yes |
Protection
method |
2 |
||||||
Connection
to ground protction |
Programmable |
Setting
range |
10-100%Ie |
Yes |
Yes |
Yes |
Yes |
Execution
delay time |
0.1-5s |
||||||
Protection
method |
0, 2 |
|
M60-1S |
M60-3S |
M60 |
M60-2P |
Control function |
||||
Direct
start |
|
|
|
|
Reversing
start |
|
|
|
|
Y-△Start |
|
|
|
|
Lower
Voltage start |
|
|
|
|
Restart
motors caused by Voltage fluctuation |
|
|
|
|
Emergency
fault output |
|
|
|
|
Local/remote
command of start, stop |
|
|
|
|
Measurement function |
||||
Operating
Current |
|
|
|
|
Unbalanced Current ratio |
|
|
|
|
Voltage,
frequency, power, power factor,leakage
current |
|
|
|
|
No. of
contact executions |
|
|
|
|
Status
of contacts |
|
|
|
|
Record Function |
||||
Latest
10 start/stop record |
|
|
Clock |
Clock |
Latest
10 alarm record |
No clock |
No clock |
Clock |
Clock |
Latest
10 trip record |
No clock |
No clock |
Clock |
Clock |
Latest
10 restart record caused by Voltage fluctuation |
|
|
Clock |
Clock |
Max.
and min. parameters records in the protection execution |
|
|
|
|
Accumulated
operating time of motor |
|
|
|
|
Communication Function |
||||
RS-485
com. Port |
|
|
|
|
Modbus
protocol |
|
|
|
|
Profibus
protocol |
|
|
|
|
Remark:
M60-3S
performs the same function as M60-1S, except that M60-3S has built-in CT,
M60-1S has exterior CT with